• DocumentCode
    1173336
  • Title

    Disturbing Load Identification in Power Systems: A Single-Point Time-Domain Method Based on IEEE 1459-2000

  • Author

    Cataliotti, Antonio ; Cosentino, Valentina

  • Author_Institution
    Dept. of Electr., Univ. di Palermo, Palermo
  • Volume
    58
  • Issue
    5
  • fYear
    2009
  • fDate
    5/1/2009 12:00:00 AM
  • Firstpage
    1436
  • Lastpage
    1445
  • Abstract
    This paper presents a single-point method for the identification of prevailing disturbing loads in power systems for both single-phase and three-phase applications downstream or upstream from the metering section. It is based on the simultaneous measurement of three nonactive power quantities, which are based on the IEEE Std. 1459-2000 approach. The proposed method is only based on the separation of the fundamental components from the harmonic content of voltage and current; thus, it does not require any spectral analysis of the voltages and current. In this paper, the formulation of the proposed method and its time-domain implementation are described; moreover, some simulation results are presented and discussed, showing the effectiveness of the method both in the absence and in the presence of the measurement transducers.
  • Keywords
    harmonic distortion; power supply quality; power system faults; power system harmonics; power system identification; power system measurement; time-domain analysis; IEEE 1459-2000; harmonic distortion; measurement transducer; metering section; power quality; power quantity measurement; power system disturbing load identification; single-point time-domain method; Harmonic distortion; IEEE 1459; power definitions; power measurements; power quality; power systems; reactive power;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.2009.2015180
  • Filename
    4787046