DocumentCode :
1173566
Title :
Investigation of Inherent Transient Recovery Voltage for Generator Circuit Breakers
Author :
Colclaser, R.G., Jr. ; Reckleff, J.G.
Author_Institution :
University of Pittsburgh
Issue :
9
fYear :
1983
Firstpage :
3000
Lastpage :
3009
Abstract :
The transient recovery voltage (TRV) for generator circuit breakers is investigated. The TRV for fault currents from the generator as well as from the system through the generator step-up transformers is calculated: A generalized expression for the TRV is developed and dimensionless plots made. Test results on two generating units are presented, showing good agreement with calculated values. A basis of rating for generator breaker TRV is also presented. TRV waveshapes and TRV parameters are suggested as part of the basis of rating.
Keywords :
Circuit breakers; Circuit faults; Circuit testing; Conductivity; Fault currents; Plasma temperature; Switchgear; Transformers; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1983.318105
Filename :
4112308
Link To Document :
بازگشت