• DocumentCode
    1173780
  • Title

    Harmonics And Reactive Power From Line-Commutated Inverters In Propposed Photovoltaic Subdivision

  • Author

    Dugan, Roger C. ; Jewell, Ward T. ; Roesler, Dietrich J.

  • Author_Institution
    McGraw-Edi son Company Power Systems Group Systems Engineering
  • Issue
    9
  • fYear
    1983
  • Firstpage
    3205
  • Lastpage
    3211
  • Abstract
    This paper describes how one hundred 6.6 kW line-commutated inverters in a proposed photovoltaic subdivision will affect the 10 MVA distribution feeder to which the inverters are connected. Voltage distortion and reactive power correction were studied using a special simulation computer program. The worst-case level of voltage total harmonic distortion is 6.2%, and by setting capacitor switching practices carefully it should be possible to keep voltage THD around 2-3%. The harmonic distortion is greatly affected by the placement of capacitors on the system.
  • Keywords
    Capacitors; Computational modeling; Computer simulation; Inverters; Photovoltaic systems; Power system harmonics; Reactive power; Solar power generation; Total harmonic distortion; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.318130
  • Filename
    4112333