DocumentCode
1173780
Title
Harmonics And Reactive Power From Line-Commutated Inverters In Propposed Photovoltaic Subdivision
Author
Dugan, Roger C. ; Jewell, Ward T. ; Roesler, Dietrich J.
Author_Institution
McGraw-Edi son Company Power Systems Group Systems Engineering
Issue
9
fYear
1983
Firstpage
3205
Lastpage
3211
Abstract
This paper describes how one hundred 6.6 kW line-commutated inverters in a proposed photovoltaic subdivision will affect the 10 MVA distribution feeder to which the inverters are connected. Voltage distortion and reactive power correction were studied using a special simulation computer program. The worst-case level of voltage total harmonic distortion is 6.2%, and by setting capacitor switching practices carefully it should be possible to keep voltage THD around 2-3%. The harmonic distortion is greatly affected by the placement of capacitors on the system.
Keywords
Capacitors; Computational modeling; Computer simulation; Inverters; Photovoltaic systems; Power system harmonics; Reactive power; Solar power generation; Total harmonic distortion; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1983.318130
Filename
4112333