• DocumentCode
    1173817
  • Title

    Lightning Surge Response Of Transmission Towers

  • Author

    Chisholm, W.A. ; Chow, Y.L. ; Srivastava, K.D.

  • Author_Institution
    Ontario Hydro
  • Issue
    9
  • fYear
    1983
  • Firstpage
    3232
  • Lastpage
    3242
  • Abstract
    A sensitivity study of HV and EHV lightning performance shows that surge response characteristics of towers and lines are as important as the footing response. Tower travel time has a very large sensitivity for taller double-circuit lines. Existing methods for analysis of tower and line response have considerable uncertainty. This uncertainty is resolved by extensions to travelling- wave analysis combined with experimental verification. New equations for tower surge impedance and tower travel time are proposed to deal with the most common situation of a midspan stroke to the skywire.
  • Keywords
    Accuracy; Corona; Dielectrics and electrical insulation; Impedance; Lightning; Optical coupling; Poles and towers; Power & Energy Society; Predictive models; Surges;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.318134
  • Filename
    4112337