• DocumentCode
    1173827
  • Title

    Development Of HVDC Thyristor Valve Insulated And Cooled By Compressed SF6 Gas

  • Author

    Matsumura, S. ; Harumoto, Y. ; Kawagoe, E. ; Tominaga, S. ; Osawa, Y. ; Yamamoto, Y. ; Marutani, T.

  • Author_Institution
    Kansai Electric Power Company
  • Issue
    9
  • fYear
    1983
  • Firstpage
    3243
  • Lastpage
    3253
  • Abstract
    A thyristor valve for HVDC transmission insulated by compressed SF6 gas has been developed. The valve is cooled by the forced circulation of the insulating gas with a blower. Valve unit up to the voltage and current ratings of 250 kV and 3,000 A can be housed in a metal tank and the valve is transportable on a trailer fully constructed. A metal enclosed converter for 500 kV HVDC power transmission for example, may be constructed by connecting the units to form a twelve pulse converter.
  • Keywords
    Cooling; Dielectrics and electrical insulation; Gas insulation; HVDC transmission; Power transmission; Sulfur hexafluoride; Testing; Thyristors; Valves; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.318135
  • Filename
    4112338