• DocumentCode
    1173980
  • Title

    HVDC Monopolar and Bipolar Cage Studies on the Corona Performance of Conductor Bundles

  • Author

    Dallaire, R.D. ; Maruvada, P. Sarma ; Rivest, N.

  • Author_Institution
    IREQ
  • Issue
    1
  • fYear
    1984
  • Firstpage
    84
  • Lastpage
    91
  • Abstract
    This paper reports on the use of test cages for obtaining the corona performance characteristics of conductor bundles under monopolar and bipolar dc excitation. A large nuimber of conductor bundles were tested under positive and negative monopolar dc as well as bipolar dc conditions in the outdoor test cages of IREQ. Radio interference (RI), audible noise (AN) and corona loss (CL) were investigated under fair weather and artificial rain. Empirical equations were derived for these three parameters: RI, AN and CL, as functions of the bundle geometry and conductor surface voltage gradient. Based on a comparison between cage and line test results, conclusions are drawn on the practical validity of cage tests for dc corona.
  • Keywords
    Acoustic noise; Conductors; Corona; Electromagnetic interference; Equations; Geometry; HVDC transmission; Rain; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318581
  • Filename
    4112356