Development of Large-Capacity, SF6 Gas Interruption Chamber and its Application to GIS
Author
Ikeda, H. ; Ueda, T. ; Kobayashi, A. ; Yamamoto, M. ; Yanabu, S.
Author_Institution
Toshiba Corporation
Issue
10
fYear
1984
Firstpage
3038
Lastpage
3043
Abstract
The gas density near the nozzle throat in a puffer- type SF6 gas, circuit breaker (GCB) is analyzed, taking into consideration the effect of gas heating by an arc. It is shown that the gas density at the current zero decreases significantly when the nozzle throat causes current clogging. It is confirmed by the experiment that interruption performance is deteriorated with a nozzle having this throat diameter. Based on this investigation, the 300kV-5OkA one- break GCB was developed. The size of the SF6 gas insulated switch- gear (GIS) which adopts the one-break GCB is so sharply reduced that one-bay-on-base transportation becomes possible.
Keywords
Analytical models; Circuit breakers; Dielectrics; Geographic Information Systems; Heating; Senior members; Substations; Sulfur hexafluoride; Switchgear; Voltage;