• DocumentCode
    1175114
  • Title

    Stability Analysis and Stabilizing Procedure for A Frequency Dependent Tansmission Line Model

  • Author

    Semlyen, Adam ; Brierley, Russell H.

  • Author_Institution
    University of Toronto
  • Issue
    12
  • fYear
    1984
  • Firstpage
    3578
  • Lastpage
    3586
  • Abstract
    A frequency dependent transmission line model, developed in 1975 and referred to in the BPA Electro-Magnetic Transients Program (EMTP) as ´Semlyen Setup´, has persistently exhibited an anomaly frustrating to its users. When the line model is isolated from the rest of the power system model by switch action it responds with an apparently linearly increasing voltage rather than a constant one corresponding to the locked charges. Experimentation has shown that the anomaly is associated with the frequency dependent characteristic admittance of the model. The paper gives the theoretical analysis of the stability of simulation, indicates the cause of the anomaly and recommends a solution. This has been tested and implemented in the EMTP.
  • Keywords
    EMTP; Frequency dependence; Power system analysis computing; Power system modeling; Power system stability; Power system transients; Power transmission lines; Stability analysis; Switches; Transmission line theory;