• DocumentCode
    1175716
  • Title

    Development of HVDC Circuit Breaker Based on Hybrid Interruption Scheme

  • Author

    Senda, T. ; Tamagawa, T. ; Higuchi, K. ; Horiuchi, T. ; Yanabu, S.

  • Author_Institution
    Electric Power Development Co., Ltd.
  • Issue
    3
  • fYear
    1984
  • fDate
    3/1/1984 12:00:00 AM
  • Firstpage
    545
  • Lastpage
    552
  • Abstract
    A hybrid interrupting unit (IU) has been examined which consists of a puffer type SF6 gas interrupting unit (GIU) and a vacuum interrupting unit (VIU) connected in series as the interrupting unit of HVDC circuit breaker (HVDC CB). Using the hybrid IU, a test of interrupting a dc current of 8 kA under a peak recovery voltage of 420 kV was conducted by means of a forced current injection method which superposes high frequency counter pulse current to dc current to produce a current zero point. Interrupting mechanism has been analyzed which applies to the transient recovery voltage period of the hybrid IU. A 250 kV -1,200 A gas insulated prototype HVDC CB has been manufactured and tested successfully.
  • Keywords
    Circuit breakers; Circuit testing; Counting circuits; Frequency; Gas insulation; HVDC transmission; Prototypes; Sulfur hexafluoride; Transient analysis; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318743
  • Filename
    4112552