• DocumentCode
    1176850
  • Title

    Analysis of Re-Ignition of Multiple Break Switches Devices Application to Shunt Reactor Current Interruption

  • Author

    Croteau, G. ; Bois-Clair, J.C. ; Jeanjean, R.

  • Author_Institution
    HYDRO-QUEBEC
  • Issue
    6
  • fYear
    1984
  • fDate
    6/1/1984 12:00:00 AM
  • Firstpage
    1377
  • Lastpage
    1385
  • Abstract
    The interruption of shunt reactor current has been studied on a Hydro-Quebec substation. The study describes the test results basedon particular characterlstics of the circuit breaker: the influence of the auxiliary chamber synchrcnism and the influence of the opening resistor values of the breaker arefirst recorded. Their theoretical models are then developed to appraise the trqrlsient voltage across the breaker terminals and the overvoltages phenomena experienced. The re-ignition, phenomena is then modeled according to the CIGRE Working Group 13-02 Recommendatatives and, a good correlation between the test results and the models output are confirmed.
  • Keywords
    Appraisal; Circuit breakers; Circuit testing; Inductors; Resistors; Shunt (electrical); Substations; Surges; Switches; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318473
  • Filename
    4112680