DocumentCode
1177246
Title
36 Pulse HVdc Transmission for Remotely Sited Generation
Author
Villablanca, M. ; delValle, J. ; Urrea, Claudio ; Rojas, W.
Author_Institution
University of Chile, Chile; SERVINSUM Ltda
Volume
21
Issue
7
fYear
2001
fDate
7/1/2001 12:00:00 AM
Firstpage
71
Lastpage
71
Abstract
Remotely sited generators that are connected to load centers may economically use HVdc transmission. The possibility of connecting the generators directly to the HVdc converter station, with both ac and dc filters removed, has been discussed frequently in the past, with significant capital and operating savings argued but as yet without such a system being realized. It would seem that the removal of filters is not feasible. In this paper a 36-pulse operation for the converter station is proposed, whereby substantial reduction of harmonics is achieved and thus both ac and dc filters may be removed without further implications.
Keywords
Active filters; Analog-digital conversion; Energy consumption; HVDC transmission; Power harmonic filters; Power system harmonics; Pulse generation; Switching frequency; Temperature distribution; Temperature sensors; HVdc converters; HVdc transmission; filters; group connection; harmonics; hydro electric generation;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2001.4311493
Filename
4311493
Link To Document