DocumentCode
1177525
Title
Evaluation on Short Line Fault Breaking Performance of SF
Gas Circuit Breaker Considering Effects of Ablated Nozzle Vapor
Author
Park, S.H. ; Kim, H.K. ; Bae, C.Y. ; Jung, H.K.
Author_Institution
Korea Electro Technol. Res. Inst., Changwon
Volume
45
Issue
3
fYear
2009
fDate
3/1/2009 12:00:00 AM
Firstpage
1836
Lastpage
1839
Abstract
In this paper, short line fault breaking performance of SF6 gas circuit breaker was evaluated by calculating the post arc current and the temperature on arc axis. For the analysis of arc-gas flow, finite volume fluid in cell method was used to solve governing equations. In arc modeling, finite element method and the method of partial characteristics were used for the calculation of Joule heating and radiation model, respectively. Also, the effect of ablated nozzle vapor was considered in the simulation. The calculated results were compared and confirmed with the experimental values.
Keywords
circuit-breaking arcs; electric breakdown; electrical faults; finite element analysis; gas blast circuit breakers; nozzles; sulphur compounds; Joule heating calculation; SF6; ablated nozzle vapor effect; arc discharges; arc-gas flow analysis; finite element method; gas circuit breaker; short line fault breaking performance; Ablation; SF$_{6}$ ; arc discharges; gas circuit breakers;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/TMAG.2009.2012805
Filename
4787452