DocumentCode
1177932
Title
A Combined Directional and Faulted Phase Selector Element Based on Incremental Quantities
Author
Benmouyal, G. ; Mahseredjian, J.
Author_Institution
Schweitzer Engineering Laboratories, Inc.; Hydro-Quebec
Volume
21
Issue
8
fYear
2001
Firstpage
61
Lastpage
61
Abstract
In this paper differential incremental or superimposed voltage and current quantities are used in order to determine directionality of a fault in a network. It is shown that this can be accomplished by performing three scalar products between three voltage and current phasor pairs. The relative levels of these same three scalar products can be furthermore used to identify the faulted phases. While, in ultra-high-speed directional comparison relays, superimposed voltage and current had to be treated in the time domain in order to get speed, in this paper all computations are done in the frequency domain.
Keywords
Circuit faults; Circuit simulation; Circuit testing; Current transformers; Digital relays; Equivalent circuits; Power system protection; Power transformers; Protective relaying; Rail transportation; Digital relaying; directional element; protective relays; single pole tripping;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2001.4311563
Filename
4311563
Link To Document