DocumentCode :
1178447
Title :
Development of a Prototype UHV Transformer and its Application to 500 kV Transformers
Author :
Okuyama, K. ; Hosi, M. ; Mori, E. ; Kashima, Y. ; Kamata, Y.
Author_Institution :
Kokubu Works Hitachi Research Lab. Hitachi Ltd.
Issue :
9
fYear :
1984
Firstpage :
2545
Lastpage :
2552
Abstract :
Development principles of an insulation structure for a prototype UHV transformer are presented. New interleaved windings having gradual apportionment of series capacitances were developed, and shown to have approximately uniform voltage distribution for lightning impulse and high reliabaility in their dielectric characteristics. The insulation structure developed for the UHV transformer was applied to a 500 kV transforrner, which allowed its floor space, weight and loss to be reduced about 20 % compared to a conventional 500 kV transformer.
Keywords :
Dielectrics and electrical insulation; Electrodes; Insulation testing; Lightning; Oil insulation; Petroleum; Power transformer insulation; Prototypes; Rail transportation; Stress;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1984.318409
Filename :
4112858