• DocumentCode
    1178590
  • Title

    230 kV Operation of a Substation Designed for 115 kV by Controlling Voltage Transients

  • Author

    Lannes, W.J. ; Priest, K.W. ; Cheramie, W.J. ; Wilhelm, M.R.

  • Author_Institution
    Louisiana Power & Light
  • Issue
    9
  • fYear
    1984
  • Firstpage
    2685
  • Lastpage
    2690
  • Abstract
    Arresters applied at the terminals of gas Insulated substations have been used successfully for protection from switching and lightning surges. This arrester application for gas Insulated substations permits the use of lower insulation levels and therefore more economical substations. In principle, the same technique can be applied to air Insulated substations. This paper describes the analysis of transient voltages In a substation designed for 115 kV which Is scheduled for operatlon at 230 kV. Both arrester rating and location are considered In this analysis. It is shown that complete substation protection is possible by addition of both arresters and capacitors.
  • Keywords
    Arresters; Capacitors; Gas insulation; Lighting control; Lightning; Substation protection; Surge protection; Switchgear; Transient analysis; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318241
  • Filename
    4112874