• DocumentCode
    1179100
  • Title

    Effect of Station Originated Outages in a Composite System Adequacy Evaluation of the IEEE Reliability Test System

  • Author

    Billinton, R. ; Vohra, P.K. ; Kumar, Sudhir

  • Author_Institution
    Power System Research Group University of Saskatchewan
  • Issue
    10
  • fYear
    1985
  • Firstpage
    2649
  • Lastpage
    2656
  • Abstract
    The reliability evaluation of a bulk power system normally includes the independent outages of generating units, transformers and transmission lines. Station originated outages, can, however, also have a significant effect on the composite system adequacy indices. Terminal station related failure events such as failures of breakers, transformers and bus sections are a major cause of multiple outages of major cxxponents (generators and/or transmission lines etc.). This paper illustrates the effects of terminal stations in composite system reliability evaluation by using the IEEE Reliability Test System (RTS). The paper also provides a valuable extension of the original RWS by including switching configurations at each bus.
  • Keywords
    Ferroelectric films; Interconnected systems; Nonvolatile memory; Power generation; Power system reliability; Power systems; Power transmission lines; Random access memory; System testing; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319105
  • Filename
    4112929