• DocumentCode
    1179440
  • Title

    Travel Time of Transmission Towers

  • Author

    Chisholm, W.A. ; Chow, Y.L. ; Srivastava, K.D.

  • Author_Institution
    Ontario Hydro
  • Issue
    10
  • fYear
    1985
  • Firstpage
    2922
  • Lastpage
    2928
  • Abstract
    In prediction of HV and EHV lightning outage rates, the tower surge response consists of two parameters, the tower impedance and the tower travel time. Of the two, tower travel time has a larger effect on the predictions. A new model for tower travel time is developed based on the relationship between tower capacitance and tower surface area. Effects of tower crossarms and other features are modelled correctly by the new theory. When the new model is used, improved lightning outage rate prediction accuracy is obtained for 500kV single circuit lines.
  • Keywords
    Accuracy; Capacitance; Insulation; Lightning; Poles and towers; Predictive models; Shape; Surface impedance; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319139
  • Filename
    4112963