DocumentCode
1179440
Title
Travel Time of Transmission Towers
Author
Chisholm, W.A. ; Chow, Y.L. ; Srivastava, K.D.
Author_Institution
Ontario Hydro
Issue
10
fYear
1985
Firstpage
2922
Lastpage
2928
Abstract
In prediction of HV and EHV lightning outage rates, the tower surge response consists of two parameters, the tower impedance and the tower travel time. Of the two, tower travel time has a larger effect on the predictions. A new model for tower travel time is developed based on the relationship between tower capacitance and tower surface area. Effects of tower crossarms and other features are modelled correctly by the new theory. When the new model is used, improved lightning outage rate prediction accuracy is obtained for 500kV single circuit lines.