DocumentCode :
1179671
Title :
Real Time Voltage-Phasor Measurement For Static State Estimation
Author :
Thorp, J.S. ; Phadke, A.G. ; Karimi, K.J.
Author_Institution :
Cornell University
Issue :
11
fYear :
1985
Firstpage :
3098
Lastpage :
3106
Abstract :
Recent introduction of microcomputers in substations to assume all substation tasks including protections makes possible accurate real-time measurements of positive sequence voltage phasors. Since static state estimators use measurements of line flows and injections to estimate the positive sequence voltage phasors it is clear that direct measurement of the state vector may be used to enhance state estimation. In order to obtain simultaneous measurements of different buses it is necessary to synchronize sampling clocks at different locations. After reviewing the techniques for obtaining positive sequence phasors from samples. techniques for clock synchronization are reviewed. Data volume reductions possible with direct measurement of state are examined and static state estimators which incorporate direct measurements are presented. Simulation results for the IEEE 118 bus system are presented.
Keywords :
Clocks; Equations; Frequency estimation; Goniometers; Phase estimation; Phase measurement; Power systems; Sampling methods; State estimation; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.318818
Filename :
4112989