• DocumentCode
    1179806
  • Title

    Voltage Recovery after Unbalanced and Balanced Voltage Dip in Three-Phase Systems

  • Author

    Bollen, Math H. J.

  • Author_Institution
    Chalmers University of Technology, Gothenburg, Sweden
  • Volume
    22
  • Issue
    10
  • fYear
    2002
  • Firstpage
    63
  • Lastpage
    64
  • Abstract
    This paper studies the recovery of the voltage after a voltage dip due to a fault in a three-phase system. The instant of voltage recovery corresponds to the instant of fault clearing. For single-phase and phase-to-phase faults a single point-on-wave of voltage recovery can be defined. For two-phase-to-ground and three-phase faults the recovery takes place in two or three steps. The voltage recovery is described in a systematic way by using a classification of three-phase unbalanced voltage dips. The voltage recovery needs to be modeled correctly for studies of equipment immunity against voltage dips.
  • Keywords
    Capacitors; Gaussian distribution; Guidelines; Harmonic analysis; Nonlinear equations; Power system harmonics; Power system modeling; Resonance; Temperature distribution; Voltage fluctuations; Power quality; equipment immunity; power transmission and distribution; voltage dips (sags);
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4311769
  • Filename
    4311769