• DocumentCode
    1180267
  • Title

    Development and Field-Data Evaluation of Single-Eng Fault Locator for Two-Thermal HVDV Transmission Lines Part I: Data Collection System and Field Data

  • Author

    Ando, M. ; Schweitzer, E.O. ; Baker, R.A.

  • Author_Institution
    Electrical and Computer Engineering Department Washington State University
  • Issue
    12
  • fYear
    1985
  • Firstpage
    3524
  • Lastpage
    3530
  • Abstract
    A prototype data collection system was developed in order to acquire field data as a part of the development of HVDC fault location techniques. The system was installed at the Celilo Converter Station of the Pacific HVDC Intertie, owned by the U. S. Department of Energy-Bonneville Power Administration in May, 1983. It monitors two line voltages, one neutral voltage, and two line currents. It also has an event detection function to trigger saving data onto a diskette. In this paper (Part I) the data collection system hardware is described, and several field data are plotted and analyzed. Development of an HVDC fault location algorithm and its evaluation using field data are given in the second paper, Part II.
  • Keywords
    Event detection; Fault location; Frequency conversion; HVDC transmission; Optical control; Optical fibers; Optical frequency conversion; Shunt (electrical); Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.318905
  • Filename
    4113052