DocumentCode
1180366
Title
Degradation of Silica-Filled Epoxy Spacers By ARC Contaminated Gases in SF6-Insulated Equipment
Author
Stuckless, H.A. ; Braun, J.M. ; Chu, F.Y.
Author_Institution
Ontario Hydro
Issue
12
fYear
1985
Firstpage
3597
Lastpage
3602
Abstract
The visual and electrical effects of arced SF6 gas on epoxy spacers with various fillers are examined. Field experience and laboratory investigations into the dielectric degradation of epoxy spacers and maintenance techniques for identifying serious loss of dielectric withstand are discussed. Rehabilitation of damaged spacers is also discussed.
Keywords
Contamination; Degradation; Dielectric losses; Gas insulation; Gases; Geographic Information Systems; Laboratories; Partial discharges; Sulfur hexafluoride; Testing;