• DocumentCode
    1180406
  • Title

    The Effect of Line Traps in the Calculation of Short Line Fault Transient Recovery Voltages

  • Author

    Jones, Robert A.

  • Author_Institution
    Southern Company Services
  • Issue
    12
  • fYear
    1985
  • Firstpage
    3625
  • Lastpage
    3633
  • Abstract
    A study of the effect of line traps on short line fault transient recovery voltages is presented. For certain conditions, line traps can cause the system transient recovery voltages (TRV) to be greater than what ANSI standards require a circuit breaker to withstand. Equivalent circuits for several types of line traps are given. An analysis is made of how the various types of line traps affect TRV. Several methods for reducing system TRV are considered.
  • Keywords
    Circuit breakers; Circuit faults; Frequency; Impedance; Power system transients; Power transmission lines; Switchgear; Transient analysis; Voltage; Wideband;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.318925
  • Filename
    4113066