DocumentCode :
1180551
Title :
An Adaptive Scheme to Prevent Undesirable Distance Protection Operation during Voltage Instability
Author :
Jonsson, Magnus ; Daalder, J.
Author_Institution :
Chalmers University of Technology, Sweden
Volume :
22
Issue :
11
fYear :
2002
Firstpage :
61
Lastpage :
61
Abstract :
An adaptive algorithm to prevent undesirable distance protection operations during voltage instability is proposed. The algorithm is based on mathematical logic blocks and uses the rate of change of voltage as an additional relay criteria to increase the relay security with respect to voltage instability. Studies are based on simulations using two different test systems: a 15-bus system developed by the authors and the Nordic32 system. The investigation shows that undesirable zone 3 distance relay operations can be the difference between a blackout and a recovering system during voltage instability. However, simulations have shown that the adaptive algorithm may save the system from a collapse. Although the algorithm prevents mal-trips due to voltage instability the reach of the distance relay will not be restricted.
Keywords :
Adaptive algorithm; Logic; Power system protection; Power system relaying; Protective relaying; Security; Stability; Substation protection; System testing; Voltage; Adaptive relaying; distance protection; remote backup; voltage stability;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4311847
Filename :
4311847
Link To Document :