DocumentCode :
1180589
Title :
Study of Abnormal Electrical Phenomena Effects on GSU Transformers
Author :
Dong, Xiaochun ; Rosado, S. ; Liu, Yanbing ; Wang, N. C. ; Wang, N. C. ; Line, E. L. ; Guo, T. Y.
Author_Institution :
Virginia Tech, USA; Taiwan Power Co., Taiwan
Volume :
22
Issue :
11
fYear :
2002
Firstpage :
62
Lastpage :
62
Abstract :
Three generator step-up (GSU) transformers successively failed in recent years in a large pumped storage plant, resulting in a considerable economic loss for the utility. A comprehensive investigation was done to find out the possible failure causes. Several aspects are considered in this study, including switching transients resulting from routine switching operations, lightning overvoltages, and harmonics and spikes due to static frequency converter (SFC) operation. The study showed that circuit breaker and disconnector restriking may affect transformer insulation due to their frequent occurrence, gas insulated switching gear (GIS) side surge arresters provide inadequate lightning protection to GSU transformers, and SFC operation has little effect on transformer insulation. This paper presents the simulation results. Methods to lower the lightning transients at the transformer terminals were provided and implemented.
Keywords :
Circuit breakers; Frequency conversion; Gas insulation; Gears; Lightning; Power transformer insulation; Surge protection; Switchgear; Switching circuits; Switching converters; GSU transformer; Pumped storage plant; harmonics; lightning; restriking; static frequency converter; switching transients; very fast transients (VFT);
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4311851
Filename :
4311851