• DocumentCode
    1180670
  • Title

    Development And Field Evaluation Of Revenue Metering Device For HVDC Systems

  • Author

    Schweitzer, E.O., III ; Ando, M. ; Aliaga, A. ; Baker, R.A. ; Seamans, D.A.

  • Author_Institution
    Department of Electrical and Computer Engineering Washington State University
  • Issue
    2
  • fYear
    1985
  • Firstpage
    416
  • Lastpage
    422
  • Abstract
    A prototype dc revenue metering device was developed under sponsorship of the Electrical Power Research Institute. The device was installed at the-Sylmar Converter Station of the Pacific HVDC Intertie, owned by the Los Angeles Department of Water and Power (host utility) in November 1981, and has been operating satisfactorily for over two years. It uses voltage and current measurements from existing voltage dividers, current transductors, and a current shunt. The energy-computation algorithms are implemented using signal processing principles in a single eight-bit microprocessor. The algorithms accommodate the different characteristics of the sensors, and tolerate the unavailability of some of the sensors, with some loss in accuracy. Comparisons of the dc revenue nieter energy measurements with the ac revenue meter measurements plus the station losses (estimated by the host utility) reveal a 0.1 percent difference in one pole and a one percent difference in the other pole, for a net difference of about one-half percent.
  • Keywords
    Current measurement; Electrical capacitance tomography; Energy measurement; HVDC transmission; Instruments; Sensor phenomena and characterization; Signal processing algorithms; Student members; Transducers; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319057
  • Filename
    4113097