DocumentCode :
1180925
Title :
Analysis of Thyristor-Controlled Shunt SSR Countermeasures
Author :
Abi-Samra, N.C. ; Smith, R.F. ; McDermott, T.E. ; Chidester, M.B.
Author_Institution :
Advanced Systems Technology Westinghouse Electric Corporation
Issue :
3
fYear :
1985
fDate :
3/1/1985 12:00:00 AM
Firstpage :
583
Lastpage :
597
Abstract :
This paper presents the results of a study to compare the effectiveness of three SSR countermeasures. Both frequency and time domain techniques were used to insure the integrity of the investigation. Reactive power modulation with generator speed feedback will damp all SSR modes if phase lags associated with thyristor firing controls are compensated. It was also found that Graetz bridge devices can damp SSR oscillations in addition to their primary functions.
Keywords :
Damping; Frequency domain analysis; Power system modeling; Rotors; Samarium; Senior members; Thyristors; Time domain analysis; Turbines; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.318976
Filename :
4113124
Link To Document :
بازگشت