Title :
Analysis of Operating Conditions of Ground-Fault Protection Schemes for Generator Stator Winding
Author :
Zielichowski, M. ; Fulczyk, Marek
Author_Institution :
Wroclaw University of Technology; ABB Corporate Research
Volume :
22
Issue :
12
fYear :
2002
Firstpage :
58
Lastpage :
58
Abstract :
This paper presents results of simulation studies of the influence of methods of grounding the stator winding of the unit-connected generator neutral on the operating conditions of a 100% ground-fault protection excited by the third harmonic voltages ratio in the generator neutral and at its terminals. The analysis was performed for a generator with the neutral grounded through a ground-fault neutralizer, a third harmonic stop filter, a resistor, and a capacitive voltage divider. The influence of the parameters of the particular elements of the grounding circuits on the voltage feeding measuring element of the protection was determined. The capacitance to ground of the generator breakers was taken into account. The simulations were run for 1,110 MVA unit-concerted generator at ground faults along the whole length of the generator stator winding. It has been found that the method of grounding the generator neutral and the parameter of the grounding elements significantly influences the operating conditions of this protection. It is shown that, through the proper selection of these parameters, the ground-fault protection of whole stator winding, counting from the generator neutral to the terminals, is ensured.
Keywords :
Circuits; Grounding; Harmonic analysis; Particle measurements; Performance analysis; Power harmonic filters; Protection; Resistors; Stator windings; Voltage measurement; Generators; fault location; grounding; protection; windings;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4311896
Filename :
4311896
Link To Document :
بازگشت