DocumentCode :
1181119
Title :
Unified Observability Analysis and Measurement Placement in Generalized State Estimation
Author :
Katsikas, P. J. ; Korres, G. N.
Author_Institution :
National Technical University of Athens, Greece
Volume :
22
Issue :
12
fYear :
2002
Firstpage :
61
Lastpage :
61
Abstract :
This paper deals with the problem of observability analysis and measurement placement in generalized state estimation, where substations are modeled at the physical-level (bus-section/switching-device model) by explicit representation of circuit breakers. The conventional state estimator is extended by incorporating the active and reactive power flows through circuit breakers as state variables. The generalized measurement model is transformed to a conventional node frame of reference formulation. Any circuit breaker (flow measured or not) is substituted by two ficticious nodes and branches, the two pairs of the corresponding voltage angles and magnitudes, and additional pseudo measurements. A very efficient numerical method is proposed for observability testing and identification of observable islands. When the network is unobservable multiple measurement placement is accomplished in a noniterative manner. Results from a test system are presented.
Keywords :
Circuit breakers; Circuit testing; Fluid flow measurement; Observability; Reactive power; State estimation; Substations; Switching circuits; System testing; Voltage; Generalized state estimation; circuit breaker; measurement placement; observability; observable islands;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4311911
Filename :
4311911
Link To Document :
بازگشت