• DocumentCode
    1181175
  • Title

    Temperature Responses to Step Changes in the Load Current of Power Transformers

  • Author

    Nordman, H. ; Rafsback, N. T. ; Susa, Dejan

  • Author_Institution
    ABB Oy; Helsinki University of Technology
  • Volume
    22
  • Issue
    12
  • fYear
    2002
  • Firstpage
    62
  • Lastpage
    62
  • Abstract
    Comprehensive load/thermal testing was performed on a 400/400/125 MVA, ONAF-cooled transformer. It was shown that the local hot-spots in the windings, core, and structural parts rise much faster at load increase than what an exponential function based on the time constant of top oil would predict. This paper analyzes these fast rises more in detail for hot-spots in windings, core, yoke clamps, and tie plates. An alternative mathematical model of the winding hot-spot response is presented. Different cooling modes, like ONAF and OFAF, are dealt with. Also different modes of oil circulation through the windings, in horizontal (zig-zag) or axial cooling ducts, are compared. The results are verified by fiberoptic installations and tests on several large power transformers in the range of 250 - 650 MVA. Hot-spot responses predicted by the IEEE Loading Guide, Annex G, are also compared to measured values.
  • Keywords
    Clamps; Cooling; Oil insulation; Performance evaluation; Petroleum; Power transformers; Temperature; Testing; Thermal loading; Transformer cores; Power transformers; temperature; windings;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4311917
  • Filename