DocumentCode
1181175
Title
Temperature Responses to Step Changes in the Load Current of Power Transformers
Author
Nordman, H. ; Rafsback, N. T. ; Susa, Dejan
Author_Institution
ABB Oy; Helsinki University of Technology
Volume
22
Issue
12
fYear
2002
Firstpage
62
Lastpage
62
Abstract
Comprehensive load/thermal testing was performed on a 400/400/125 MVA, ONAF-cooled transformer. It was shown that the local hot-spots in the windings, core, and structural parts rise much faster at load increase than what an exponential function based on the time constant of top oil would predict. This paper analyzes these fast rises more in detail for hot-spots in windings, core, yoke clamps, and tie plates. An alternative mathematical model of the winding hot-spot response is presented. Different cooling modes, like ONAF and OFAF, are dealt with. Also different modes of oil circulation through the windings, in horizontal (zig-zag) or axial cooling ducts, are compared. The results are verified by fiberoptic installations and tests on several large power transformers in the range of 250 - 650 MVA. Hot-spot responses predicted by the IEEE Loading Guide, Annex G, are also compared to measured values.
Keywords
Clamps; Cooling; Oil insulation; Performance evaluation; Petroleum; Power transformers; Temperature; Testing; Thermal loading; Transformer cores; Power transformers; temperature; windings;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4311917
Filename
4311917
Link To Document