• DocumentCode
    1181204
  • Title

    Comparison of SSR calculations and test results

  • Author

    Katz, Edward ; Tang, Ju ; Bowler, C.E.J. ; Farmer, R.G. ; Cruz, Cristovao ; Sims, Jennifer

  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    2/1/1989 12:00:00 AM
  • Firstpage
    336
  • Lastpage
    344
  • Abstract
    A summary is given of presentations made at a panel session at the 1987 Winter and Summer Power Meeting of the IEEE Power Engineering Society. Topics of discussion include turbine-generator characteristics, the sharing of machine damping with multiple units on line, load modeling, measurement of system impedance, and comparison of tested and calculated damping. The discussions focused on comparisons of the calculated versus measured subsynchronous resonance (SSR) quantities. SSR case studies of two systems are presented with the overall calculated damping or undamping compared with system tests
  • Keywords
    damping; resonance; turbogenerators; SSR calculations; load modeling; machine damping; subsynchronous resonance; turbine-generator characteristics; Capacitors; Damping; Equations; Hazards; Impedance; Load modeling; Magnetic analysis; Power system modeling; Resonance; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.32497
  • Filename
    32497