  • Abstract
    Under many circumstances, the initiation of breakdown can be viewed as conversion of energy stored in the electric field (capacitive energy) to thermal energy which converts matter in a thin channel from a nonconducting state to a conducting plasma. This paper analyzes this process in the context of breakdown in SF6 as a prelude to a second paper that treats the subject of breakdown under highly inhomogeneous thermal field, quasi-homogeneous electric field conditions.
  • Keywords
    Band pass filters; Cooling; Electric breakdown; Lubricating oils; Oil insulation; Petroleum; Sulfur hexafluoride; Testing; Transformers; Transient analysis; Breakdown; GIS; SF6; gaseous dielectrics;