DocumentCode :
1181308
Title :
Effect of Surge Wave Reflection Inside a Motor On Voltage Distribution Across Stator Windings
Author :
Nassar, O.M.
Issue :
4
fYear :
1985
fDate :
7/1/1985 12:00:00 AM
Firstpage :
881
Lastpage :
889
Abstract :
A study was conducted to evaluate the need for surge protection of large motors in NGL plants. Power system analysis indicated that motor winding insulation can withstand lightning and switching surges. Motor surge protection was not installed as a result. The investigation of subsequent failure of four 21,000 HP motors indicated that motor winding failures occurred due to high magnitude switching surges. The test results of winding insulation surge withstand level and voltage distribution across coils are presented. The repetitive insulation failure of the second coil in all four motors is explained.
Keywords :
Cables; Insulation; Lightning; Reflection; Stator windings; Surge protection; Switchgear; Synchronous motors; Transformers; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.319089
Filename :
4113169
Link To Document :
بازگشت