DocumentCode
1181896
Title
Discussion of "Measurement of /spl lambda/-i characteristics of asymmetric three-phase transformers and their applications"
Author
Martynaitis, J.
Author_Institution
Dept. of Electr. & Lighting Eng., Kaunas Univ. of Technol., Lithuania
Volume
18
Issue
2
fYear
2003
fDate
4/1/2003 12:00:00 AM
Firstpage
641
Abstract
The author argues that the main contribution of the original paper (see ibid., vol.17, p.983-90, 2002) is the definition of symmetric /spl lambda/-i characteristics for asymmetric three-phase transformers with three limbs. The analysis shows that such transformers have magnetizing currents with more than one maximum and minimum. Such three-limb transformers are relatively insensitive to the generation of reactive power Q-and the resulting voltage drop V-due to balanced DC currents caused by imperfect gating, geomagnetically induced currents, and nuclear explosions producing a low-frequency pulse. In this paper , the author asks various questions about the original authors´ results.
Keywords
load (electric); power transformer testing; transformer cores; transformer windings; /spl lambda/-i characteristics measurement; applications; asymmetric loads; asymmetric three-phase transformers; no-load; paper discussion; symmetric loads; three-limb cores; DC generators; Iron; Nuclear power generation; Phase transformers; Power engineering and energy; Power generation; Power system analysis computing; Power system measurements; Reactive power; Transformer cores;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.809748
Filename