Harmonic Resposnse Tests on Voltage Transducers for the New Zealand Power System
Author
Bradley, D.A. ; Bodger, P.S. ; Hyland, P.R.
Author_Institution
University of Lancaster
Issue
7
fYear
1985
fDate
7/1/1985 12:00:00 AM
Firstpage
1750
Lastpage
1756
Abstract
This paper presents the results of harmonic response tests carried out on capacitive voltage transformers, as used on the New Zealand 220 kV a.c. network. It is shown that the harmonic response measured using low voltage test equipment is considerably different from that obtained at high voltage. The latter is highly non-linear and is affected by the specific magnetization characteristic of the CVT tested. It is concluded that for field measurement of harmonics at rated voltage, the transformer of a CVT unit should be disconnected and the CVT used as a purely capacitive or resistor-capacitor divider.
Keywords
Low voltage; Magnetic field measurement; Magnetization; Power system harmonics; Power system measurements; System testing; Test equipment; Transducers; Voltage measurement; Voltage transformers;