• DocumentCode
    1182172
  • Title

    Harmonic Resposnse Tests on Voltage Transducers for the New Zealand Power System

  • Author

    Bradley, D.A. ; Bodger, P.S. ; Hyland, P.R.

  • Author_Institution
    University of Lancaster
  • Issue
    7
  • fYear
    1985
  • fDate
    7/1/1985 12:00:00 AM
  • Firstpage
    1750
  • Lastpage
    1756
  • Abstract
    This paper presents the results of harmonic response tests carried out on capacitive voltage transformers, as used on the New Zealand 220 kV a.c. network. It is shown that the harmonic response measured using low voltage test equipment is considerably different from that obtained at high voltage. The latter is highly non-linear and is affected by the specific magnetization characteristic of the CVT tested. It is concluded that for field measurement of harmonics at rated voltage, the transformer of a CVT unit should be disconnected and the CVT used as a purely capacitive or resistor-capacitor divider.
  • Keywords
    Low voltage; Magnetic field measurement; Magnetization; Power system harmonics; Power system measurements; System testing; Test equipment; Transducers; Voltage measurement; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319208