DocumentCode :
1182179
Title :
Correction of Phase Voltage Measurements Referenced to an Ungrounded Neutral
Author :
Grady, W.M. ; Taylor, W.L.
Author_Institution :
Dept. of Electrical Engineering University of Texas
Issue :
7
fYear :
1985
fDate :
7/1/1985 12:00:00 AM
Firstpage :
1757
Lastpage :
1760
Abstract :
Recording voltmeters are often used to provide a permanent record of three phase bus voltages. If the meters are improperly installed, using an ungrounded neutral, the recorded phase to neutral voltages can indicate severely unbalanced conditions, even for a balanced system. The purpose of this paper is to present a Newton-Raphson based iterative solution technique which can be used to reconstruct balanced three phase voltage phasors from unbalanced recorded values which were mistakenly referenced to an ungrounded neutral.
Keywords :
Capacitors; Customer service; Instruments; Phase measurement; Power cables; Power industry; Steel; Substations; Voltage measurement; Voltmeters;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.319209
Filename :
4113295
Link To Document :