Title :
Transient Recovery Voltage Behind Transformer : Calculation and Measurement
Author :
Sabot, A.
Author_Institution :
Electricitéance
Issue :
7
fYear :
1985
fDate :
7/1/1985 12:00:00 AM
Firstpage :
1916
Lastpage :
1921
Abstract :
This paper is dealing with transient recovery voltage (TRV) of circuit breaker located behind transformer. Based on theory and experiments, it tries to clarify the notion of amplitude factor. According to previous measurements it gives a relation between amplitude factor and inherent frequency of transformers and a method to calculate this frequency. The actual parameters of TRV can be measured with a simple method.
Keywords :
Circuit breakers; Circuit faults; Equivalent circuits; Frequency measurement; Measurement standards; Power measurement; Shape; Switchgear; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.318757
Filename :
4113321
Link To Document :
بازگشت