DocumentCode
1182448
Title
Pipe-Type Cable Losses for Balanced and Unbalanced Currents
Author
Kuang, Jingming ; Boggs, Steven
Author_Institution
University of Toronto, Canada; University of Connecticut, Storrs, CT
Volume
22
Issue
3
fYear
2002
fDate
3/1/2002 12:00:00 AM
Firstpage
57
Lastpage
57
Abstract
Computations of pipe eddy current losses have been undertaken for balanced and unbalanced current using a program for transient nonlinear finite element analysis developed by one of the authors. Good agreement is obtained with experimental data from the literature. The computations indicate that the eddy current losses reach a minimum around 700 A conductor current. Experimental data are available only to about 800 A, so that this phenomenon has not been reported previously and may have an impact on rated ampacities for high pressure fluid filled (HPFF) cable. Computations for unbalanced currents indicate increased losses with increasing unbalance, as expected.
Keywords
Aging; Coatings; Conductors; Degradation; Eddy currents; Electrodes; Power cables; Power distribution lines; Space technology; Wire; HPFF; eddy current losses; pipe-type cable;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312058