• DocumentCode
    1182448
  • Title

    Pipe-Type Cable Losses for Balanced and Unbalanced Currents

  • Author

    Kuang, Jingming ; Boggs, Steven

  • Author_Institution
    University of Toronto, Canada; University of Connecticut, Storrs, CT
  • Volume
    22
  • Issue
    3
  • fYear
    2002
  • fDate
    3/1/2002 12:00:00 AM
  • Firstpage
    57
  • Lastpage
    57
  • Abstract
    Computations of pipe eddy current losses have been undertaken for balanced and unbalanced current using a program for transient nonlinear finite element analysis developed by one of the authors. Good agreement is obtained with experimental data from the literature. The computations indicate that the eddy current losses reach a minimum around 700 A conductor current. Experimental data are available only to about 800 A, so that this phenomenon has not been reported previously and may have an impact on rated ampacities for high pressure fluid filled (HPFF) cable. Computations for unbalanced currents indicate increased losses with increasing unbalance, as expected.
  • Keywords
    Aging; Coatings; Conductors; Degradation; Eddy currents; Electrodes; Power cables; Power distribution lines; Space technology; Wire; HPFF; eddy current losses; pipe-type cable;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312058
  • Filename
    4312058