Title :
Currents of Synchronous Machines Immediately Following A Disturbance
Author :
Szablya, John F.
Author_Institution :
EBASCO SERVICES INCORPORATED
Abstract :
The transient currents of synchronous machines are investigated up to some 5 miliseconds duration following a short circuit. The conventional representation, namely two (or more) network frequency, decaying ac and one single exponential aperiodic dc, does not hold in this range. As a matter of fact, the dc component may even increase for a short time following a disturbance. High speed digital sampling techniques have to take this phenomenon into account.
Keywords :
Angular velocity; Circuits; Digital relays; Electrical fault detection; Frequency; Power engineering; Sampling methods; Stators; Synchronous machines; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :