DocumentCode
1183214
Title
Factory Overload Testing of a Large Power Transformer
Author
Douglas, D.H. ; Lawrence, C.O. ; Templeton, J.B.
Author_Institution
The Cleveland Electric Illuminating Company
Issue
9
fYear
1985
Firstpage
2492
Lastpage
2500
Abstract
A factory overload test of up to 150% of the nameplate rating was run on a 224 MVA autotransformer. The results of this test were of great value and were used in identifying transformer overload limitations, in evaluating loading guide oil and winding equations, exponents and time constants, and in helping to perfect a factory overload test procedure.
Keywords
Equations; Heating; Oil insulation; Performance evaluation; Petroleum; Power transformers; Production facilities; Pulp manufacturing; Substations; Testing;
fLanguage
English