Abstract :
A factory overload test of up to 150% of the nameplate rating was run on a 224 MVA autotransformer. The results of this test were of great value and were used in identifying transformer overload limitations, in evaluating loading guide oil and winding equations, exponents and time constants, and in helping to perfect a factory overload test procedure.
Keywords :
Equations; Heating; Oil insulation; Performance evaluation; Petroleum; Power transformers; Production facilities; Pulp manufacturing; Substations; Testing;