• DocumentCode
    1183390
  • Title

    Design and Analysis of the Inverter-Side Filter Used in the Dynamic Voltage Restorer

  • Author

    Choi, S. S. ; Li, B. H. ; Vilathgamuwa, D. Mahinda

  • Author_Institution
    Nanyang Technological University, Singapore
  • Volume
    22
  • Issue
    4
  • fYear
    2002
  • fDate
    4/1/2002 12:00:00 AM
  • Firstpage
    80
  • Lastpage
    80
  • Abstract
    The role of the inverter-side filter used in the dynamic voltage restorer (DVR) is examined. Using the circuit analysis method, it is shown that the selection of the filter parameters can affect the DVR inverter rating. Furthermore, with the DVR filter-series injection transformer combination, the loading effect of the filter on the restorer and the primary supply system has been quantified under normal as well as voltage sag conditions. A systematic filter design method is then proposed, the primary objective of which is to achieve specific harmonic performance while ensuring that the DVR inverter rating and the loading effect are minimized. Illustrative examples are also included.
  • Keywords
    Abstracts; Circuit analysis; Harmonic analysis; Industrial power systems; Inverters; Load flow; Power harmonic filters; Power system harmonics; Static VAr compensators; Voltage fluctuations; Dynamic voltage restorer; filter; harmonics; voltage sag;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312158
  • Filename
    4312158