DocumentCode :
1183509
Title :
Protection technique based on Δ-zero sequence voltages for generator stator ground fault
Author :
Tai, N.L. ; Ai, Q.
Author_Institution :
Dept. of Power Electr. Eng., Shanghai Jiao Tong Univ., China
Volume :
151
Issue :
5
fYear :
2004
Firstpage :
651
Lastpage :
657
Abstract :
A mathematical model on a coil basis is used to study the characteristics of the zero sequence voltage of a generator. The proposed technique for the stator ground fault detection simultaneously takes into account the fault contributed zero sequence fundamental voltage and the fault contributed third-harmonic voltage (Δ-zero sequence voltage). The effect of the start-up component based on the wavelet transform is also highlighted. As information both on the fault contributed zero sequence fundamental voltage and the third-harmonic voltage is used simultaneously, the scheme can obtain higher sensitivity. Results from the experiment and in the field show that the proposed technique can detect the ground fault with high sensitivity and reliability during all operating conditions.
Keywords :
coils; electric generators; fault diagnosis; harmonic distortion; harmonics suppression; machine protection; reliability; stators; wavelet transforms; Δ-zero sequence voltages; coils; fault contributed third-harmonic voltage; fundamental voltage; generator fault; mathematical model; protection technique; reliable operating conditions; sensitivity; start-up component; stator ground fault detection; wavelet transform;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20040644
Filename :
1367431
Link To Document :
بازگشت