DocumentCode
1183679
Title
Natural Contamination test of Insulators at Noto Testing Station Near Japan Sea
Author
Taniguchi, Y. ; Arai, N. ; Imano, Y.
Author_Institution
Technical Laboratory Hokuriku Electric Power Company, Inc.
Issue
1
fYear
1979
Firstpage
239
Lastpage
245
Abstract
This paper describes the results of investigation into the performance of various types of insulators energized with 200 kV ac and ±280 kV dc voltages and exposed to natural conditions by the seaside for about five years. DC voltage application had almost the same influence on the salt deposit density as ac voltage application. Salt deposit density and flashover characteristics of insulators were much affected by their types. Flashover voltage for dc is almost the same as that for ac in rms value.
Keywords
Circuit testing; Flashover; Insulation; Insulator testing; Laboratories; Power engineering and energy; Sea measurements; Sea surface; Surface contamination; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1979.319524
Filename
4113470