• DocumentCode
    1183679
  • Title

    Natural Contamination test of Insulators at Noto Testing Station Near Japan Sea

  • Author

    Taniguchi, Y. ; Arai, N. ; Imano, Y.

  • Author_Institution
    Technical Laboratory Hokuriku Electric Power Company, Inc.
  • Issue
    1
  • fYear
    1979
  • Firstpage
    239
  • Lastpage
    245
  • Abstract
    This paper describes the results of investigation into the performance of various types of insulators energized with 200 kV ac and ±280 kV dc voltages and exposed to natural conditions by the seaside for about five years. DC voltage application had almost the same influence on the salt deposit density as ac voltage application. Salt deposit density and flashover characteristics of insulators were much affected by their types. Flashover voltage for dc is almost the same as that for ac in rms value.
  • Keywords
    Circuit testing; Flashover; Insulation; Insulator testing; Laboratories; Power engineering and energy; Sea measurements; Sea surface; Surface contamination; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319524
  • Filename
    4113470