• DocumentCode
    1183882
  • Title

    The Laboratory Investigation of a Digital System for the Protection of Transmission Lines

  • Author

    Breingan, W.D. ; Chen, M.M. ; Gallen, T.F.

  • Author_Institution
    General Electric Company
  • Issue
    2
  • fYear
    1979
  • fDate
    3/1/1979 12:00:00 AM
  • Firstpage
    350
  • Lastpage
    368
  • Abstract
    The results and conclusions of a feasibility study of a digital system for the protection of transmission lines are presented. In this laboratory investigation, a computer with its data acquisition system was connected to a transmission line model. The minicomputer program for a two-zone stepped-distance protection scheme utilizes an algorithm based on the system differential equation. Extensive testing with a wide range of fault types, fault locations, fault inception angles, and power flows demonstrated the success of the system. Trip times were on the average equal to or less than 0.5 cycle for the primary protection zone. The program successfully determined fault type and location with the fault locations usually within a mile over the range of the model of a 72 mile transmission line.
  • Keywords
    Data acquisition; Differential equations; Digital systems; Fault location; Laboratories; Microcomputers; Power system modeling; Power system protection; Power transmission lines; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319326
  • Filename
    4113493