DocumentCode
1183882
Title
The Laboratory Investigation of a Digital System for the Protection of Transmission Lines
Author
Breingan, W.D. ; Chen, M.M. ; Gallen, T.F.
Author_Institution
General Electric Company
Issue
2
fYear
1979
fDate
3/1/1979 12:00:00 AM
Firstpage
350
Lastpage
368
Abstract
The results and conclusions of a feasibility study of a digital system for the protection of transmission lines are presented. In this laboratory investigation, a computer with its data acquisition system was connected to a transmission line model. The minicomputer program for a two-zone stepped-distance protection scheme utilizes an algorithm based on the system differential equation. Extensive testing with a wide range of fault types, fault locations, fault inception angles, and power flows demonstrated the success of the system. Trip times were on the average equal to or less than 0.5 cycle for the primary protection zone. The program successfully determined fault type and location with the fault locations usually within a mile over the range of the model of a 72 mile transmission line.
Keywords
Data acquisition; Differential equations; Digital systems; Fault location; Laboratories; Microcomputers; Power system modeling; Power system protection; Power transmission lines; Transmission lines;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1979.319326
Filename
4113493
Link To Document