• DocumentCode
    1183980
  • Title

    Sensitivity of Transformer´s Hottest Spot and Equivalent Aging to Selected Parameters

  • Author

    Peterchuck, D. ; Pahwa, Anil

  • Author_Institution
    Omaha Public Power District; Kansas State University
  • Volume
    22
  • Issue
    5
  • fYear
    2002
  • fDate
    5/1/2002 12:00:00 AM
  • Firstpage
    70
  • Lastpage
    70
  • Abstract
    In 1995, IEEE released a revised Transformer Loading Guide, which includes an Annex G that contains an additional set of transformer temperature equations that incorporate oil flow phenomena, changing ambient air temperature, and account for the change in resistivity of the winding due to heating. These new equations involve empirical exponent variables that account for properties of the transformer. This paper investigates sensitivity of hottest spot temperature and equivalent aging of transformer with respect to these variables. By varying these variables under various load conditions and by Monte Carlo simulation with different probability distributions of these variables, their importance in the transformer model and their influence in modeling accuracy pertaining to the Annex G equations have been obtained.
  • Keywords
    Aging; Equations; Magnetic flux; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Surges; Temperature sensors; Testing; Monte Carlo methods; Power transformer; insulation aging; transformer windings;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312223
  • Filename
    4312223