DocumentCode :
1184025
Title :
A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power Shift
Author :
Mahat, Pukar ; Chen, Zhe ; Bak-Jensen, Birgitte
Author_Institution :
Inst. of Energy Technol., Aalborg Univ., Aalborg
Volume :
24
Issue :
2
fYear :
2009
fDate :
4/1/2009 12:00:00 AM
Firstpage :
764
Lastpage :
771
Abstract :
The mainly used islanding detection techniques may be classified as active and passive techniques. Passive techniques don´t perturb the system but they have larger non-detection zones, whereas active techniques have smaller non-detection zones but they perturb the system. In this paper, a new hybrid technique is proposed to solve this problem. An average rate of voltage change (passive technique) has been used to initiate a real power shift (active technique), which changes the real power of distributed generation (DG), when the passive technique cannot have a clear discrimination between islanding and other events in the system. Simulation results show that the proposed method is effective in detecting islanding of distribution systems with DGs.
Keywords :
distributed power generation; active technique; distributed generation; hybrid islanding detection technique; passive techniques; real power shift; Distributed generation; islanding detection; real power shift; voltage change;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2013376
Filename :
4797808
Link To Document :
بازگشت