DocumentCode :
1184243
Title :
Increasing of ground resistance of human foot in substations´ yards
Author :
Thapar, B. ; Alaywan, Ziad A.
Author_Institution :
Montana State Univ., Bozeman, MT, USA
Volume :
4
Issue :
3
fYear :
1989
fDate :
7/1/1989 12:00:00 AM
Firstpage :
1695
Lastpage :
1700
Abstract :
In a substation switchyard use of a plastic sheet immediately below the layer of crushed rock or the cement concrete pathway is proposed at locations where a high value of the grounding resistance of the human foot is required. A method to evaluate the grounding resistance of the foot when the plastic sheet is used is given. A procedure to estimate the reduction in the grounding resistance of the foot caused by a hole in the plastic sheet is proposed. The results have also been obtained through scale model studies. They compare favorably with the results obtained through the method proposed. Comparison of the touch potential with and without the plastic sheet is presented
Keywords :
earthing; electric resistance; plastics; substations; cement concrete pathway; crushed rock; grounding resistance; human foot; plastic sheet; substations´ yards; touch potential; Concrete; Foot; Grounding; Humans; Immune system; Plastics; Soil; Substations; Surface resistance; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.32661
Filename :
32661
Link To Document :
بازگشت