DocumentCode
1184312
Title
Seismic behaviour of toughened glass station post insulators for 800 kV networks
Author
Grases, J. ; Lopez, O.A. ; Parraud, R. ; Joulie, R. ; Bourdier, G.
Author_Institution
Central Univ. of Caracas, Venezuela
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1701
Lastpage
1707
Abstract
The results of tests on 800 kV toughened glass post insulators are presented and analytical study to define their dynamic behavior when associated with connections and a supporting chassis under extreme service conditions (earthquake, short-circuit) is described. The findings show that the performance of toughened glass post insulators under high-amplitude dynamic loads permits even the most stringent specifications to be satisfied with a high safety margin. Under forced vibrations, the acceleration at the top of the insulator necessary to cause breakage was 5.6 g (g =9.81 m/s2), which is at least three times larger than that required by specifications for Venezuela and the US West Coast
Keywords
glass; insulators; safety; substations; testing; 800 kV; US West Coast; Venezuela; breakage; forced vibrations; high-amplitude dynamic loads; safety margin; seismic behaviour; substations; tests; toughened glass post insulators; Earthquakes; Failure analysis; Glass; Insulation; Insulator testing; Mortar; Safety; Stress; Substations; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32662
Filename
32662
Link To Document