• DocumentCode
    1184384
  • Title

    Measurements of RIV on Large EHV Apparatus in High Voltage Laboratory

  • Author

    Golinski, Jacek ; Malewski, Ryszard ; Train, David

  • Author_Institution
    Instytut Elektrotechniki
  • Issue
    3
  • fYear
    1979
  • fDate
    5/1/1979 12:00:00 AM
  • Firstpage
    817
  • Lastpage
    824
  • Abstract
    North American practice for the measurement of Radio Interference Voltage, (RIV), on EHV apparatus is specified by the NEMA 107 Standard. The recommended measurement frequency is 1 MHz but at this frequency physically large test circuits do not represent the service condition. The measured levels of RIV for EHV apparatus may be unrealistically high at 1 MHz. This phenomenon is caused by an increase of RIV signals due to an internal resonance in the test circuit. This increased reading cannot be corrected by the application of the Circuit RIV Factor "p" since the circuit responses of the calibration and test set-ups are different.
  • Keywords
    Calibration; Circuit testing; Electromagnetic interference; Frequency measurement; Laboratories; Measurement standards; RLC circuits; Radiofrequency integrated circuits; Resonance; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319294
  • Filename
    4113550