DocumentCode
1184384
Title
Measurements of RIV on Large EHV Apparatus in High Voltage Laboratory
Author
Golinski, Jacek ; Malewski, Ryszard ; Train, David
Author_Institution
Instytut Elektrotechniki
Issue
3
fYear
1979
fDate
5/1/1979 12:00:00 AM
Firstpage
817
Lastpage
824
Abstract
North American practice for the measurement of Radio Interference Voltage, (RIV), on EHV apparatus is specified by the NEMA 107 Standard. The recommended measurement frequency is 1 MHz but at this frequency physically large test circuits do not represent the service condition. The measured levels of RIV for EHV apparatus may be unrealistically high at 1 MHz. This phenomenon is caused by an increase of RIV signals due to an internal resonance in the test circuit. This increased reading cannot be corrected by the application of the Circuit RIV Factor "p" since the circuit responses of the calibration and test set-ups are different.
Keywords
Calibration; Circuit testing; Electromagnetic interference; Frequency measurement; Laboratories; Measurement standards; RLC circuits; Radiofrequency integrated circuits; Resonance; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1979.319294
Filename
4113550
Link To Document