• DocumentCode
    1184441
  • Title

    Dynamic Stability Improvvement at Monticello Station-Analytical Study and Field Tests

  • Author

    Busby, E.L. ; Hurley, J.D. ; Keay, F.W. ; Raczkowski, C.

  • Author_Institution
    Texas Utilities Services Inc.
  • Issue
    3
  • fYear
    1979
  • fDate
    5/1/1979 12:00:00 AM
  • Firstpage
    889
  • Lastpage
    901
  • Abstract
    Turbine-generator Units #1 and #2 at the Texas Utilities Monticello Station were found to be dynamically unstable when operating near full load and connected to the power system by a single transmission line. Power system stabilizers (PSS) were applied to the excitation systems to provide stable operation under these conditions. Suitable settings for the PSS were predetermined analytically by frequency response and root locus analysis of a single machine-infinite bus configuration. A 3rd order generator model is shown to be adequate for this type of analysis. Dynamic performance measured in field tests is in close agreement with calculated performance.
  • Keywords
    Power generation; Power system analysis computing; Power system dynamics; Power system modeling; Power system stability; Power transmission lines; Protective relaying; Regulators; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319301
  • Filename
    4113557