DocumentCode :
1184556
Title :
High Frequency Switching Surges in EHV Shunt Reactor Installation with Reduced Insulation Levels
Author :
Sarkinen, Stephen H. ; Schockelt, Guenter G. ; Brunke, John H.
Author_Institution :
Bonneville Power Administration
Issue :
3
fYear :
1979
fDate :
5/1/1979 12:00:00 AM
Firstpage :
1013
Lastpage :
1021
Abstract :
When de-energizing shunt reactors with load interrupters, reignitions are likely to occur. The resulting high frequency transients have been investigated for a typical EHV installation by computer studies and field tests. These transients can be eliminated or minimized by controlling the instant of contact parting. They can also be reduced by low ohmic opening resistors.
Keywords :
Arresters; Costs; Dielectrics and electrical insulation; Frequency; Inductors; Interrupters; Shunt (electrical); Substation protection; Surge protection; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1979.319259
Filename :
4113569
Link To Document :